VectraShield™-605B
Corrosion Inhibitor
Products
Industrial Recirculating Cooling Water Treatment
• VectraShield™-D05BW
• VectraShield™-D05Q
• VectraShield™-3210C
• VectraShield™-605A
• VectraShield™-605B
• VectraShield™-C06
• VectraShield™-991Y
• VectraShield™-993
• VectraShield™-995
VectraShield™-605B
Scale Inhibitor
|
Product |
Corrosion Inhibitor |
|
|
Model |
VectraShield™-605B |
|
|
Application |
– |

Introduction
- This circulating cooling water corrosion inhibitor is an efficient composite water‑treatment chemical, formulated with organophosphorus components and special synergistic corrosion‑inhibiting agents. The product is acidic and is designed to be used in combination with a separate scale inhibitor for open‑loop industrial circulating cooling water systems.
- When dosed independently, it forms a dense, adherent protective film on carbon‑steel and mild‑steel surfaces of pipelines, heat exchangers and cooling tower structures, suppressing uniform corrosion and pitting corrosion. Separate dosing of corrosion inhibitor and scale inhibitor allows respective dosage adjustments. This operational mode ensures both anti‑corrosion and scale‑control performances are maintained even under high concentration‑ratio operating conditions.
- It exhibits good compatibility with alkaline‑formulated scale inhibitors and common oxidizing / non‑oxidizing biocides for cooling‑water treatment.
- Typical Applications: Waste‑to‑energy plants, thermal power stations, chemical plants, steel mills and general‑purpose manufacturing industrial circulating cooling water systems. Always apply together with matched circulating‑water scale inhibitor.
Technical Analysis Indicators
|
Item |
Indicator |
|---|---|
|
Appearance |
Light yellow to brownish yellow transparent liquid |
|
Solid Content,% |
≧ 20.0 |
|
Density(20℃),g/cm3 |
≧ 1.10 |
|
|
2.0±1.5 |
|
Solubility |
Fully miscible with water |
Recommended Operating Conditions
|
Item |
Indicator |
|---|---|
|
Parameter |
Suggested Range |
|
Circulating water pH |
7.0~9.2 |
|
Total hardness (as CaCO₃) |
≤ 950 mg/L |
|
Total alkalinity (as CaCO₃) |
≤ 750 mg/L |
|
Concentration ratio |
≧ 6.0 cycles |
|
Dosage |
12‑35 mg/L |
Usage and method of application:
- Use an independent automatic metering pump for continuous dosing. Inject into cooling‑water basin or suction side of circulating‑water pump. **Do NOT mix concentrated corrosion‑inhibitor stock solution with concentrated scale‑inhibitor stock solution in the same tank**.
- Maintain stable residual concentration in circulating loop. Perform regular water‑quality analysis and corrosion‑rate monitoring to adjust dosing quantity.
- Used together with corresponding scale inhibitor; biocides shall be added at separate dosing points to avoid high‑concentration direct contact with undiluted chemical agents.
- If mixing with other water‑treatment chemicals is required, dilute each agent with water in advance.
- For new systems or heavily corroded old systems, complete pre‑filming treatment prior to normal continuous dosing.
Package,storage and safety:
- 25 Litre Drum(25kg per drum)/210 Litre Drum(200kg per drum)/IBCs(1000kg per drum).
- Store in cool, dry and well‑ventilated warehouse; keep container tightly sealed. Avoid direct sunlight and freezing.
- Shelf‑life: 12 months under proper storage.
- Wear chemical‑resistant gloves and goggles when handling. Avoid contact with eyes and skin. In case of contact, rinse thoroughly with plenty of clean water.
- Dispose waste liquid in accordance with local environmental regulations. Do not discharge raw product directly into water bodies.